Ask Question
1 September, 01:49

In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement, NEC 404.9 (B) requires the use of what kind of faceplate

+1
Answers (2)
  1. 1 September, 02:22
    0
    A metal faceplate with grounding means

    Explanation:

    metal faceplate with grounding means is required in older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement.
  2. 1 September, 03:15
    0
    The NEC requires the use of a metallic faceplate for this situation.

    Explanation:

    NEC 404.9 (B) requires a metal faceplate having a means for grounding to be used in older installations where there is no ground for an equipment in a metal box switch located within a conductive floor. There is however an exception which states that as long as the wiring method does not have anything to do with an equipment-grounding conductor, it is required that a snap switch that is wired and located within reach of conductive floors must have a nonmetal faceplate or protected by an interrupter.
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a ...” in 📙 Computers & Technology if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.