Ask Question
1 September, 08:24

A room that has an average ambient sound pressure level of 62 dBA and a maximum sound pressure level lasting more than a minute at 68 dBA must have a public mode signal that is at least?.

+1
Answers (1)
  1. 1 September, 11:04
    0
    A fire alarm notification appliance is an active fire protection component of a fire alarm system. The primary function of the notification appliance is to alert persons at risk.

    If want the audible public mode signal to be hear clearly then, we need to have a sound level that is at least 15dB above the average ambient sound level or 5dB above the maximum sound level of at least 1minute

    In this case the,

    The average ambient sound level is 62dB,

    And the maximum sound level is 68dB

    Then, the public mode signal should be at least

    1. 62dB + 15dB=77dB

    Or

    2. 68dB + 5dB = 73dB.

    Then the public mode signal hearing must be at least 77dB.
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “A room that has an average ambient sound pressure level of 62 dBA and a maximum sound pressure level lasting more than a minute at 68 dBA ...” in 📙 Physics if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.
Search for Other Answers