A refrigeration system is to cool bread loaves with an average mass of 350 g from 30 to - 10°C at a rate of 1200 loaves per hour with refrigerated air at - 30°C. Taking the average specific and latent heats of bread to be 2.93 kJ/kg·°C and 109.3 kJ/kg, respectively, determine (a) the rate of heat removal from the breads, in kJ/h (b) the required volume flow rate of air, in m3/h, if the temperature rise of air is not to exceed 8°C (c) the size of the compressor of the refrigeration system, in kW, for a COP of 1.2 for the refrigeration system.

+4
Answers (1)
  1. 30 October, 18:39
    0
    rate of removal of heat is 100566 KJ/h

    volume flow rate is 8626.35 m³/h

    size of compressor is 23.83 kW

    Explanation:

    Given data

    mass m = 350 g = 0.37 kg

    temperature T1 = - 10°C

    temperature T2 = 30°C

    number of cool bread loaves = 1200

    average specific heat = 2.93 kJ/kg·°C

    latent heats = 109.3 kJ/kg

    solution

    we will find here first mass rate of bread that is = number of cool bread * mass

    mass rate bread = 1200 * 0.37 = 444 kg/h = 0.123 kg/s

    so removal of heat = sum of heat of bread and heat of freeze

    so removal of heat = mass of bread C (T2-T1) + mass of bread * latent heat

    removal of heat = 444 (2.93) (30 - (-10)) + (444 * 109.3)

    so rate of removal of heat = 100566 KJ/h

    and

    we know that specific heat of air = 1.005 kJ/kg from property of ideal gas table

    so volume flow rate is mass of air / density of air

    and density of air = P/RT

    density = 101.325 / 0.287 (-30+273)

    density = 1.45 kg/m³

    so mass flow rate = mass of air * C * (Δt)

    100566 = mass of air (1.005) 8

    mass of air = 12508.208 kg/h

    so volume flow rate will be = mass of air / density

    volume flow rate = 12508.208 / 1.45 = 8626.35 m³/h

    and

    power capacity of compressor = heat removal / size of compressor

    so

    size of compressor = 100566 / 1.2 = 83805 kJ/h = 23.83 kW

    so size of compressor is 23.83 kW
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “A refrigeration system is to cool bread loaves with an average mass of 350 g from 30 to - 10°C at a rate of 1200 loaves per hour with ...” in 📙 Physics if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.