What is the internal heat gain, in kW, from a factory with 20 kW of lighting (surface-mounted), 10 kW of running motors, and 10 people doing light benchwork?

+4
Answers (1)
  1. 29 April, 07:39
    0
    Internal Heat Gain = 35 KW

    Explanation:

    The internal heat gain can be calculated as:

    Internal Heat Gain = Heat gain due to lights + Heat gain due to motor + Heat gain due to people

    Here, we assume an average heat gain of 500 W per person. Therefore,

    Heat gain due to people = (0.5 KW) (10)

    Heat gain due to people = 5 KW

    Therefore, using values in the equation, we get:

    Internal Heat Gain = 20 KW + 10 KW + 5 KW

    Internal Heat Gain = 35 KW
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “What is the internal heat gain, in kW, from a factory with 20 kW of lighting (surface-mounted), 10 kW of running motors, and 10 people ...” in 📙 Physics if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.