Ask Question
3 July, 08:47

A one-family dwelling contains an electric range rated at 25 kw. what is the neutral load demand for this range

+1
Answers (1)
  1. 3 July, 11:28
    0
    In the load calculations stipulated in Article 220 of the National Electrical Code, branch circuits must not be undersized for safety purposes. In industrial applications, there are always 'rule of thumbs'. The exact calculations are a product of ideal conditions. But in reality, there are heat losses through the conductor materials. Therefore, it is mandatory that a safety factor should be incorporated. For the calculation of the neutral load, it is a rule of thumb to apply a demand factor of 70% for household electrical appliances like the oven, dryers and cooking ranges. Therefore, the minimum neutral demand load for this range is 25 kW * 0.7 = 17.5 kW.
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “A one-family dwelling contains an electric range rated at 25 kw. what is the neutral load demand for this range ...” in 📙 Physics if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.
Search for Other Answers