An air conditioner using refrigerant R-134a as the working fluid and operating on the ideal vapor-compression refrigeration cycle is to maintain a space at 22°C while operating its condenser at 1000 kPa.

a. Determine the COP of the system when a temperature difference of 2°C is allowed for the transfer of heat in the evaporator.

+3
Answers (1)
  1. 28 July, 22:47
    0
    COP=13.37

    Explanation:

    Considering the allowed temperature difference the temperature in the evaporator will be 20°. The enthalpy and entropy at this temperature are obtained from table for the saturated vapor phase:

    h_1=261.64 kJ/kg

    s_1=0.92254 kJ/kgK

    The enthalpy at state 2 is determined from the given condenser pressure and the condition s_2 = s_1 with data from table using interpolation:

    h_2=273.18 kJ/kg

    The enthalpy at states 3 and 4 is determined from the saturated liquid value for the condenser pressure from table:

    h_3=h_4=107.34 kJ/kg

    the COP is then:

    COP=qL/w

    = h_1 - h_4 / h_2 - h_1

    =13.37
Know the Answer?
Not Sure About the Answer?
Get an answer to your question ✅ “An air conditioner using refrigerant R-134a as the working fluid and operating on the ideal vapor-compression refrigeration cycle is to ...” in 📙 Engineering if there is no answer or all answers are wrong, use a search bar and try to find the answer among similar questions.